Tank testing · TX

Houston

Underground storage tank testing in Houston, Texas.

Verified Provider Directory — 4 listings in Houston

Names, websites, phones, and service areas are copied from each company’s own site. IKECA is shown only when that site lists the certification. Facility Inspect does not grade companies and does not show star ratings.

Authority having jurisdictionHouston Fire Department

Houston’s restaurant and hospitality kitchens cover every volume tier in the NFPA 96 table. Inside the city limits, confirm the adopted code with the Houston Fire Department. A kitchen outside the city may answer to a different authority.

No account

Request free compliance quotes

Quotes for Houston. Change the city if the site is next door.

Email or phone is required. A quote also needs the business name, type, and timeline. The form posts to /api/quote. A contractor is contacted only after delivery is configured for this deployment. Nothing here is a booked service.Privacy

Federal UST baselines

These are the federal baselines in 40 CFR 280.35 and 280.36. A state program can be stricter, and double-walled equipment that is monitored on the walkthrough cycle can follow that option instead of the three-year test. Confirm the rule with the state UST program before you hire.

40 CFR 280 walkthroughs and tests
OperationInterval
Walkthrough, spill prevention and release detectionVisual check of spill equipment, and a check that release detection is operating without alarms. Spill equipment at sites with infrequent deliveries may be checked before each delivery instead.40 CFR 280.36Every 30 days
Walkthrough, sumps and handheld devicesContainment sumps, and handheld release-detection devices such as gauge sticks or bailers.40 CFR 280.36Annually
Spill buckets and piping sumpsLiquid-tight test of spill prevention equipment and of containment sumps used for interstitial monitoring of piping, unless both walls of double-walled equipment are monitored on the walkthrough cycle.40 CFR 280.35Every 3 years
Overfill preventionInspection that overfill equipment is set to activate at the required level and will activate when product reaches it.40 CFR 280.35Every 3 years

Federal rule and EPA source