Sprinkler and fire-alarm inspection in Atlanta, Georgia.
Verified Provider Directory — 3 listings in Atlanta
Sprinkler inspection
Atlanta
Source: Company website
Sprinkler inspection · Alarm inspection
Atlanta and North Georgia
Source: Company website
Sprinkler inspection · Alarm inspection
Atlanta, Kennesaw, Cobb County, and greater Metro Atlanta
Source: Company website
Names, websites, phones, and service areas are copied from each company’s own site. IKECA is shown only when that site lists the certification. Facility Inspect does not grade companies and does not show star ratings.
This page is the City of Atlanta, not the metro counties around it. Neighborhood and downtown kitchens span the NFPA 96 tiers. Confirm the adopted code with Atlanta Fire Rescue Department.
NFPA 25 and NFPA 72 intervals
NFPA 25 assigns a different interval to each part of a water-based system. NFPA 72 does the same for alarm devices. This is the short set owners run into most often, not the full ITM table. The edition adopted by the Atlanta Fire Rescue Department governs.
| Operation | Interval |
|---|---|
| Sealed control valvesInspection. Locked or electrically supervised valves are on a monthly inspection instead. | Weekly |
| GaugesInspection on wet systems. Replacement or calibration is a separate multi-year item. | Monthly |
| Waterflow alarmsTest of the alarm device. Supervisory devices have their own row in the ITM table. | Quarterly |
| Sprinklers, pipe, and hangersInspection. A main drain test is annual, and quarterly where the supply passes through a backflow or pressure-reducing valve. | Annually |
| Fire pumpNo-flow (churn) test: weekly for diesel, monthly for electric. A full flow test is annual. | Weekly / monthly |
| Alarm devicesSmoke detectors, heat detectors, manual stations, and notification appliances. Control-unit inspection is more frequent when the panel is not monitored. | Annually |